TYPE UL MV105 SINGLE CONDUCTOR SHIELDED EPR INSULATION PVC JACKET COPPER POWER CABLE 24kV / 35kV

TYPE UL MV105 SINGLE CONDUCTOR SHIELDED EPR INSULATION PVC JACKET COPPER POWER CABLE 24kV / 35kV
Specification
Power Cable
25KV 133% Insulation Level 
35KV 100% Insulation Level
UL Type MV-105, 105°C
Single Conductor, Shielded
EPR Insulation, PVC Jacket 
Copper Conductor

Application:

Appropriate for all situations of corrosive environments in power circuits up to 24,000V / 35,000V in all installations of open air, conduit, and duct, cable tray when CT rated, in wet and dry locations. Main uses are for chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code permitted for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:

Has a semi-conducting conductor shield, with soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact).

Insulation:

Ethylene propylene rubber (EPR) per ICEA S-97-682 with a semi-conducting insulation shield.

Shield:

Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.

Jacket:

Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072. 

Standards:

  • ICEA S-93-639
  • NEMA WC74
  • AEIC CS8
  • Federal Specification J-C-30B

Specification

Power Cable
25KV 133% Insulation Level 
35KV 100% Insulation Level
UL Type MV-105, 105°C
Single Conductor, Shielded
EPR Insulation, PVC Jacket 
Copper Conductor

Application:

Appropriate for all situations of corrosive environments in power circuits up to 24,000V / 35,000V in all installations of open air, conduit, and duct, cable tray when CT rated, in wet and dry locations. Main uses are for chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. National Electric Code permitted for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductor:

Has a semi-conducting conductor shield, with soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact).

Insulation:

Ethylene propylene rubber (EPR) per ICEA S-97-682 with a semi-conducting insulation shield.

Shield:

Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.

Jacket:

Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072. 

Standards:

  • ICEA S-93-639
  • NEMA WC74
  • AEIC CS8
  • Federal Specification J-C-30B

Details

Frequently Asked Questions - TYPE UL MV105 SINGLE CONDUCTOR SHIELDED EPR INSULATION PVC JACKET COPPER POWER CABLE 24kV / 35kV Power Cable

What are the specific applications of Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper24kV/35kV Power Cables?

Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper 24kV/35kV Power Cables are suitable for corrosive environments in power circuits up to 24,000V / 35,000V which are installed in open air, conduit & duct; cable tray when CT rated, in wet and dry conditions. These power cables are appropriate for chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and general stations.


How is the Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper24kV/35kV Power Cable constructed? What materials are used for conductors and insulators?

Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper 24kV/35kV Power Cables is constructed using a semi-conducting conductor shield of soft bare annealed copper which qualify the ASTM B-3. It also has Class B stranding as per ASTM B-8 (compressed) or ASTM B-496 (compact).

For insulation, these power cables use a semi-conducting insulation shield of Ethylene propylene rubber (EPR) that qualifies the ICEA S-97-682 standard.

They have an uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682 for shielding. It also has a sunlight resistant PVC Jacket.


What are the regulations and uses of  Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper24kV/35kV Power Cables under specific temperature conditions?

The National Electric Code has allowed the use of Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper 24kV/35kV Power Cables at 105°C for continuous operation, 140°C for emergency overload conditions and 250°C for short circuit conditions.

 

What sizes of power cables are available in Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper24kV/35kV Power Cables range?

Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper 24kV/35kV Power Cables are available through 8 AWG – 1000 MCM. Specifics can be found at http://www.crownindustrial.com/med-epr-sheild-24-35-kv.html.

 

What type of Jacket does the Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper24kV/35kV Power Cables have?

For Jacket, Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper 24kV/35kV Power Cables are having sunlight resistant PVC as per the standards of ICEA S-97-682 and UL Standard 1072.


What are the national and international standards to which Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper24kV/35kV Power Cables conform?

Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper 24kV/35kV Power Cables conforms to all major national and international technical standards of the industry such as:

  • ICEA S-93-639
  • NEMA WC74
  • AEIC CS8
  • Federal Specification J-C-30B