Okoguard-Okolon TS-CPE Type MV-105 - 140 mils

Okoguard-Okolon TS-CPE Type MV-105 - 140 mils
Specification

Applications
Okoguard shielded Okolon TS-CPE Type MV-105 power cables are recommended for use as feeder circuits in electric utility generating stations, for distribution circuits, and for feeders or branch circuits in industrial and commercial installations.
Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250.4(A)(5), or messenger supported in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be installed in cable tray.

  Product Name
Length
Price (Per FT.)
 

115-23-2917 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 6 AWG

FT.
Call 516-472-0650 for pricing

115-23-2919 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 4 AWG

FT.
Call 516-472-0650 for pricing

115-23-2921 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 2 AWG

FT.
Call 516-472-0650 for pricing

115-23-2923 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 1 AWG

FT.
Call 516-472-0650 for pricing

115-23-2925 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 1/0 AWG

FT.
Call 516-472-0650 for pricing

115-23-2927 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 2/0 AWG

FT.
Call 516-472-0650 for pricing

115-23-2929 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 3/0 AWG

FT.
Call 516-472-0650 for pricing

115-23-2931 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 4/0 AWG

FT.
Call 516-472-0650 for pricing

115-23-2933 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 250 MCM AWG

FT.
Call 516-472-0650 for pricing

115-23-2937 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 350 MCM AWG

FT.
Call 516-472-0650 for pricing

115-23-2949 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 750 MCM AWG

FT.
Call 516-472-0650 for pricing

115-23-2951 Okoguard-Okolon TS-CPE Type MV-105 - 140 mils - 1000 MCM AWG

FT.
Call 516-472-0650 for pricing

Specification

Applications
Okoguard shielded Okolon TS-CPE Type MV-105 power cables are recommended for use as feeder circuits in electric utility generating stations, for distribution circuits, and for feeders or branch circuits in industrial and commercial installations.
Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried if installed in a system with a grounding conductor in close proximity that conforms with NEC Section 250.4(A)(5), or messenger supported in industrial establishments and electric utilities. Sizes 1/0 AWG and larger may also be installed in cable tray.

Details

Insulation
Okoguard is Okonite’s registered trade name for its exclusive ethylene-propylene rubber (EPR) based, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.
The triple tandem extrusion of the screens with the insulation provides optimum electrical characteristics.

Jacket
The Okolon TS-CPE jacket on this cable is a vulcanized chloronated polyethylene base compound which is mechanically rugged, flame, radiation, and oil resistant.

Specifications
Conductor: Annealed uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 or UL 1072.
Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3, and UL 1072.
Insulation Screen: Extruded semiconducting EPR insulation screen. Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.3 and UL 1072.
Shield: 5 mil bare copper tape helically applied with 25% nominal overlap.
Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, CSA C68.3 and UL 1072 for chloronated polyethylene jackets.
UL Listed as Type MV-105, sunlight resistant and for use in cable tray in accordance with UL 1072.
CSA C68-3 listed and rated FT4 (1/0 and larger) and -40°C.

Product Features

  • Triple tandem extruded, all EPR system.
    Okoguard cables meet or exceed all recognized industry standards (UL, CSA,AEIC, NEMA/ICEA, IEEE, CSA).
  • 105°C continuous operating temperature.
  • 140°C emergency rating.
  • 250°C short circuit rating.
  • Passes UL and IEEE 383 and 1202 (1/0 AWG and larger) Vertical Tray Flame Test.
  • Excellent corona resistance.
  • Screens are clean stripping.
  • Exceptional resistance to “treeing”.
  • Exceptional resistance to moisture.
  • Resistant to most oils, acids, and alkalies.
  • Sunlight resistant.
  • For Cable Tray Use; 1/0 AWG and
  • larger.
  • CSA FT4 and -40°C.
  • Improved Temperature Rating.