Okoguard Okoseal Type MV-105 5/8kV Shielded Power Cable - 3 Okopact

Okoguard Okoseal Type MV-105 5/8kV Shielded Power Cable - 3 Okopact
Specification

Applications

Okoguard shielded three conductor Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits in industrial & utility power distribution systems. Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried, cable tray, or messenger supported in industrial establishments and electric utilities.

Insulation
Okoguard Is Okonite's registered trade name for its exclusive ethylene-propylene rubber (EPR) base, thermosetting compound, whose optimum balance of electrical and physical properties is unequaled in other solid dielectrics. Okoguard insulation, with the distinctive red color and a totally integrated EPR system, provides the optimum balance of electrical and physical properties for long, problem free service.

Assembly
The Type MV-105 conductors are assembled with fillers and a binder tape overall. One bare stranded copper ground conductor is placed in one of the outer interstices.

Jacket
The Okoseal (PVC) jacket supplied with this cable is mechanically rugged and has excellent resistance to oil and most chemicals.

Conductors: Uncoated copper compact stranded per ASTM B-496.
Strand Screen: Extruded semiconducting EPR strand screen meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072.
Insulation: Okoguard meets or exceeds the electrical and physical requirements of ICEA S-93-639/NEMA WC74 and UL 1072. The insulated conductors are tested in accordance with AEIC CS8.
Insulation Screen: Extruded semiconducting EPR insulation screen per ICEA S-93-639/NEMA WC74, AEIC CS8 and UL 1072.
Shield: 5 mil uncoated copper tape helically applied with 12.5% nominal overlap.
Phase Identification: Color coded (black, red, blue) polyester ribbon laid longitudinally under the copper shield.
Grounding Conductor: Uncoated copper compact stranded per ASTM B-496 and sized in accordance with UL 1072.
Assembly: Cabled with fillers and ground wire in the interstices, binder tape overall.
Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93- 639/NEMA WC74 and UL 1072 for polyvinyl chloride jackets.
UL Listed as Type MV-105, sunlight resistant for use in cable tray, and for direct burial in accordance with UL 1072.
Cables listed to CSA C68.3 are also available.

Product Features

  • Triple tandem extruded, all EPR system.
  • Complete prepackaged, color coded, factory tested wiring system.
  • Passes the vertical tray flame test requirements of IEEE 383 and UL 1072.
  • Complies with NEC Sections 310-7 and 710-4(b) for direct burial.
  • Excellent corona resistance.
  • Screens are clean stripping.
  • Exceptional resistance to “treeing”.
  • Improved Temperature Rating.

Specification

Applications

Okoguard shielded three conductor Type MV-105 power cables are recommended for distribution circuits, and for feeders or branch circuits in industrial & utility power distribution systems. Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried, cable tray, or messenger supported in industrial establishments and electric utilities.

Details

Okoguard Okoseal Type MV-105 5/8kV Shielded Power Cable - 3 Okopact

Thistype MV-105 power cable is designed to help in power distributions in medium voltages that do not exceed 105 volts. This cable has three conductors with individual insulation. They are shielded with a braided copper for maximum performance. A grounding conductor is longitudinally bonded on the shielded conductors. The grounding conductors act as the neutral path. OkoguardOkoseal Type MV-105 cable is jacketed for chemical and mechanical protection. Assembly of this cable is assembled with a binder tape and fillers.

Conductor

The conductors are made of compacted copper in accordance to ASTM B496 requirements. Copper is a good electrical conductor with low current resistance.

Standards and Certifications

The cable is in line with the following standards:

• ASTM B-496
• Underwriters Laboratory (UL) 1072
• ICEA S-93-639 or NEMA WC74
• AEIC CS8
• IEEE 383
• National Engineers Code (NEC) section 310-7

Insulation

This type of Multi-conductor cable is insulated with Ethylene Propylene Rubber (EPR). The EPR is a thermosetting compound and thus can withstand extreme temperature conditions. It is semi-conducting and will not subject the user to electric shocks when handling it. Ethylene Propylene Rubber offers a superb chemical protection from the corrosive industrial chemicals, which would cause corrosion to Okoguard Type MV Power Cable. EPR is also tough enough to withstand abrasions.

Shielding

This cable is shielded with 5 mil bare copper tape, which is helically applied. It offers 12.5% nominal overlap hence improving the electrical conductivity of the cable. Shielding provides an additional protection from direct mechanical attacks on Okoguard Power Cables.

Jacketing

This is the outer layer which is color coded for easy identification. It is made of the Polyvinyl Chloride (PVC) which is mechanically rugged, and provides resistance to moisture and oil. PVC is also non-biodegradable and will not succumb to fungal attacks.

Applications

• Industrial power systems
• Utility power systems

Write Your Own Review

You're reviewing: Okoguard Okoseal Type MV-105 5/8kV Shielded Power Cable - 3 Okopact

How do you rate this product? *

 
1 1 star
2 2 star
3 3 star
4 4 star
5 5 star
Quality
Price
Value